5.3.9 Technical revision history
Table 530: TRPPTRC Technical revision history
Technical revision Change
B -
C -
D Internal improvement.
E Setting
Trip output mode
default setting is
changed to "Latched".
F Internal improvement.
5.4 Fault locator SCEFRFLO
5.4.1 Identification
Function description IEC 61850
identification
IEC 60617
identification
ANSI/IEEE
C37.2 device
number
Fault locator SCEFRFLO FLOC 21FL
5.4.2 Function block
Figure 247: Function block
5.4.3 Functionality
The fault locator function SCEFRFLO provides impedance-based fault location. It
is designed for radially operated distribution systems. It is applicable for locating
short circuits in all kinds of distribution networks. Earth faults can be located in
effectively earthed and in low-resistance or low-reactance earthed networks. Under
certain limitations, SCEFRFLO can also be applied for an earth-fault location in
unearthed distribution networks.
Protection related functions