3.17.3.4 Settings
PTGAPC Non group settings (Basic)
Table 156: PTGAPC Non group settings (Basic)
Parameter Values (Range) Unit Step Default Description
Pulse time 1 0...3600000 ms 10 0 Pulse time
Pulse time 2 0...3600000 ms 10 0 Pulse time
Pulse time 3 0...3600000 ms 10 0 Pulse time
Pulse time 4 0...3600000 ms 10 0 Pulse time
Pulse time 5 0...3600000 ms 10 0 Pulse time
Pulse time 6 0...3600000 ms 10 0 Pulse time
Pulse time 7 0...3600000 ms 10 0 Pulse time
Pulse time 8 0...3600000 ms 10 0 Pulse time
3.17.3.5 Technical data
Table 157: PTGAPC Technical data
Characteristic Value
Operate time accuracy ±1.0% of the set value or ±20 ms
3.17.4 Daily timer function DTMGAPC
3.17.4.1 Identification
Function description IEC 61850
identification
IEC 60617
identification
ANSI/IEEE C37.2
device number
Daily timer function DTMGAPC DTMGAPC DTMGAPC
3.17.4.2 Function block
Figure 85: Function block
3.17.4.3 Functionality
The Daily timer function DTMGAPC is used to activate or deactivate the output at
the set time of the day. It is possible to set different activation or deactivation times
separately for each day of the week.