Parameter Values
(Range)
Unit Step Defaul
t
Description
LNKLIV
Up
Down
Link status of redundant port LAN
A. Valid only when
Redundant mode
is set to "HSR" or "PRP".
REDLNKLIV
Up
Down
Link status of redundant port LAN
B. Valid only when
Redundant mode
is set to "HSR" or "PRP".
3.20.1.4 Settings
Redundancy settings
Table 217: Redundancy settings
Parameter Values
(Range)
Unit Step Defaul
t
Description
Redundant
mode
None
PRP
HSR
None Mode selection for Ethernet switch
on redundant communication mod-
ules. The "None" mode is used with
normal and Self-healing Ethernet
topologies.
3.20.1.5 Monitored data
Monitored data is available in four locations.
Monitoring> Communication> Ethernet> Activity> CHLIV_A
Monitoring> Communication/> Ethernet> Activity> REDCHLIV_B
Monitoring> Communication> Ethernet> Link statuses> LNKLIV_A
Monitoring> Communication> Ethernet> Link statuses> REDLNKLIV_B
3.20.2 Ethernet channel supervision SCHLCCH
3.20.2.1 Function block
Figure 111: Function block
3.20.2.2 Functionality
Ethernet channel supervision SCHLCCH represents X1/LAN, X2/LAN and X3/LAN
Ethernet channels.
An unused Ethernet port can be set "Off" with the setting Configuration>
Communication> Ethernet> Rear port(s)> Port x Mode. This setting closes the
1MRS758755 C
Basic functions
REC615 & RER615
Technical Manual
211