6.1.7 Settings
6.1.7.1 TCSSCBR Non group settings
Table 551: TCSSCBR Non group settings (Basic)
Parameter Values (Range) Unit Step Default Description
Operation
1=on
5=off
1=on Operation Off / On
Operate delay time 20...300000 ms 1 3000 Operate delay time
Table 552: TCSSCBR Non group settings (Advanced)
Parameter Values (Range) Unit Step Default Description
Reset delay time 20...60000 ms 1 1000 Reset delay time
6.1.8 Monitored data
6.1.8.1 TCSSCBR Monitored data
Table 553: TCSSCBR Monitored data
Name Type Values (Range) Unit Description
TCSSCBR Enum
1=on
2=blocked
3=test
4=test/blocked
5=off
Status
6.1.9 Technical revision history
Table 554: TCSSBR Technical revision history
Technical revision Change
B Internal improvement
C Internal improvement
6.2 Fuse failure supervision SEQSPVC