3.16.8.3 Signals
Table 95: T_TCMD_BIN input signals
Name Type Default Description
IN INT32 0 Input signal
Table 96: T_TCMD_BIN output signals
Name Type Description
RAISE BOOLEAN Raise command
LOWER BOOLEAN Lower command
3.16.9 T_BIN_TCMD function block
3.16.9.1 Function block
Figure 63: Function block
3.16.9.2 Functionality
The T_BIN_TCMD function is used to convert Boolean input signals to 32 bit integer
output signals.
Table 97: Conversion from Boolean to integer
RAISE LOWER OUT
FALSE FALSE 0
FALSE TRUE 1
TRUE FALSE 2
3.16.9.3 Signals
Table 98: T_BIN_TCMD input signals
Name
Type Default Description
RAISE BOOLEAN 0 Raise command
LOWER BOOLEAN 0 Lower command
1MRS758755 C Basic functions
REC615 & RER615
Technical Manual
131