Name Type Values (Range) Unit Description
AI_DB5 FLOAT32 -10000.0...10000 .0 RTD input, Connectors 9-10-11c, reported
value
AI_RANGE5 Enum
0=normal
1=high
2=low
3=high-high
4=low-low
RTD input, Connectors 9-10-11c, range
AI_DB6 FLOAT32 -10000.0...10000 .0 RTD input, Connectors 13-14-12c, repor-
ted value
AI_RANGE6 Enum
0=normal
1=high
2=low
3=high-high
4=low-low
RTD input, Connectors 13-14-12c, range
AI_DB7 FLOAT32 -10000.0...10000 .0 RTD input, Connectors 15-16-12c, repor-
ted value
AI_RANGE7 Enum
0=normal
1=high
2=low
3=high-high
4=low-low
RTD input, Connectors 15-16-12c, range
AI_DB8 FLOAT32 -10000.0...10000 .0 RTD input, Connectors 17-18-12c, repor-
ted value
AI_RANGE8 Enum
0=normal
1=high
2=low
3=high-high
4=low-low
RTD input, Connectors 17-18-12c, range
3.14 SMV function blocks
SMV function blocks are used in the process bus applications with the sending of
the sampled values of analog currents and voltages and with the receiving of the
sampled values of voltages.
3.14.1 IEC 61850-9-2 LE sampled values sending SMVSENDER
3.14.1.1 Functionality
The SMVSENDER function block is used for activating the SMV sending functionality.
It adds/removes the sampled value control block and the related data set into/from
the sending device's configuration. It has no input or output signals.
SMVSENDER can be disabled with the
Operation
setting value “off”. If the
SMVSENDER is disabled from the LHMI, it can only be enabled from the LHMI. When
disabled, the sending of the samples values is disabled.