Table 565: MDSOPT Non group settings (Advanced)
Parameter Values (Range) Unit Step Default Description
Initial value 0...299999 h 1 0 Initial value for op-
eration time super-
vision
Operating time
hour
0...23 h 1 0 Time of day when
alarm and warning
will occur
Operating time
mode
1=Immediate
2=Timed Warn
3=Timed Warn Alm
1=Immediate Operating time
mode for warning
and alarm
6.3.8 Monitored data
6.3.8.1 MDSOPT Monitored data
Table 566: MDSOPT Monitored data
Name Type Values (Range) Unit Description
MDSOPT Enum
1=on
2=blocked
3=test
4=test/blocked
5=off
Status
OPR_TIME INT32 0...299999 h Total operation
time in hours
6.3.9 Technical data
Table 567: MDSOPT Technical data
Description Value
Motor runtime measurement accuracy 
1
±0.5 %
6.3.10 Technical revision history
Table 568: MDSOPT Technical revision history
Technical revision Change
B Internal improvement.
C Internal improvement.
D Internal improvement.
1
Of the reading, for a stand-alone relay, without time synchronization
1MRS758755 C Supervision functions