ABB Relion REC615 - Monitored Data; Technical Data; Technical Revision History

ABB Relion REC615
869 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Table 565: MDSOPT Non group settings (Advanced)
Parameter Values (Range) Unit Step Default Description
Initial value 0...299999 h 1 0 Initial value for op-
eration time super-
vision
Operating time
hour
0...23 h 1 0 Time of day when
alarm and warning
will occur
Operating time
mode
1=Immediate
2=Timed Warn
3=Timed Warn Alm
1=Immediate Operating time
mode for warning
and alarm
6.3.8 Monitored data
6.3.8.1 MDSOPT Monitored data
Table 566: MDSOPT Monitored data
Name Type Values (Range) Unit Description
MDSOPT Enum
1=on
2=blocked
3=test
4=test/blocked
5=off
Status
OPR_TIME INT32 0...299999 h Total operation
time in hours
6.3.9 Technical data
Table 567: MDSOPT Technical data
Description Value
Motor runtime measurement accuracy
1
±0.5 %
6.3.10 Technical revision history
Table 568: MDSOPT Technical revision history
Technical revision Change
B Internal improvement.
C Internal improvement.
D Internal improvement.
1
Of the reading, for a stand-alone relay, without time synchronization
1MRS758755 C Supervision functions
REC615 & RER615
Technical Manual