EasyManua.ls Logo

ABB Relion REC615 - Settings; Monitored Data

ABB Relion REC615
869 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
10.2.6.1 VMHAI Input signals
Table 705: VMHAI Input signals
Name Type Default Description
U_A_AB SIGNAL 0 Phase-to-earth volt-
age A or phase-to-
phase voltage AB
U_B_BC SIGNAL 0 Phase-to-earth volt-
age B or phase-to-
phase voltage BC
U_C_CA SIGNAL 0 Phase-to-earth volt-
age C or phase-to-
phase voltage CA
BLOCK BOOLEAN 0=False Block signal for all bi-
nary outputs
10.2.6.2 VMHAI Output signals
Table 706: VMHAI Output signals
Name Type Description
ALARM BOOLEAN Alarm signal for THD
10.2.7 Settings
10.2.7.1 VMHAI Non group settings (Basic)
Table 707: VMHAI Non group settings (Basic)
Parameter Values (Range) Unit Step Default Description
Operation
1=on
5=off
1=on Operation Off / On
Demand interval
0=1 minute
1=5 minutes
2=10 minutes
3=15 minutes
4=30 minutes
5=60 minutes
6=180 minutes
2=10 minutes Time interval for
demand calculation
Demand window
1=Sliding
2=Non-sliding
1=Sliding Demand calculation
window type
THD alarm limit 1.0...100.0 % 0.1 50.0 THD alarm limit
Power quality measurement functions 1MRS758755 C
706 REC615 & RER615
Technical Manual

Table of Contents

Other manuals for ABB Relion REC615