Parameter Values (Range) Unit Step Default Description
2=phase-to-phase phase-to- phase
voltages
Phase supervi-
sion
1=A or AB
2=B or BC
3=A&B or AB&BC
4=C or CA
5=A&C or AB&CA
6=B&C or BC&CA
7=A&B&C or
AB&BC&CA
4=C or CA Monitored volt-
age phase
Num of phases 1=1 out of 3
2=2 out of 3
3=3 out of 3
1=1 out of 3 Number of pha-
ses required for
voltage supervi-
sion
V live value 0.2...1.0 xUn 0.1 0.5 Limit value for
high voltage
V live time 40...10000 ms 1 100 Duration time for
high voltage
V dead value 0.1...0.8 xUn 0.1 0.2 Limit value for
low voltage
V dead time 40...10000 ms 1 100 Duration time for
low voltage
Table 572: PHSVPR Non group settings (Advanced)
Parameter Values
(Range)
Unit Step Default Description
Relative hystere-
sis
1.0...5.0 % 0.1 4.0 Relative hysteresis for volt-
age supervision
6.4.8 Monitored data
Table 573: PHSVPR Monitored data
Name Type Values (Range) Unit Description
PHSVPR Enum 1=on
2=blocked
3=test
4=test/blocked
5=off
Status
Supervision functions 1MRS758755 C
550 REC615 & RER615