Parameter Values (Range) Unit Step Default Description
5=off
Min operate current 0.01...1.00 xIn 0.01 0.10 Minimum operating
current
Min operate volt-
age
0.01...1.00 xUn 0.01 0.30 Minimum operating
voltage
Table 500: DPSRDIR Non group settings (Advanced)
Parameter Values (Range) Unit Step Default Description
Reset delay time 0...60000 ms 1 20 Reset delay time
4.6.1.8 Monitored data
Table 501: DPSRDIR Monitored data
Name Type Values (Range) Unit Description
ANGLE_RCA FLOAT32 -180.00...180.00 deg Angle between operat-
ing angle and charac-
teristic angle
DPSRDIR Enum 1=on
2=blocked
3=test
4=test/blocked
5=off
Status
4.7 Multipurpose protection MAPGAPC
4.7.1 Identification
Function description IEC 61850
identification
IEC 60617
identification
ANSI/IEEE C37.2
device number
Multipurpose protection MAPGAPC MAP MAP
4.7.2 Function block
Figure 231: Function block
1MRS758755 C
Protection functions
REC615 & RER615
Technical Manual
471