8.1.6 Residual current measurement RESCMMXU
8.1.6.1 Identification
Function description IEC 61850
identification
IEC 60617
identification
ANSI/IEEE
C37.2 device
number
Residual current measurement RESCMMXU Io In
8.1.6.2 Function block
Figure 296: Function block
8.1.6.3 Signals
RESCMMXU Input signals
Table 600: RESCMMXU Input signals
Name Type Default Description
Io SIGNAL 0 Residual current
BLOCK BOOLEAN 0=False Block signal for all bi-
nary outputs
RESCMMXU Output signals
Table 601: RESCMMXU Output signals
Name Type Description
HIGH_ALARM BOOLEAN High alarm
HIGH_WARN BOOLEAN High warning
8.1.6.4 Settings
RESCMMXU Non group settings
Table 602: RESCMMXU Non group settings (Basic)
Parameter Values (Range) Unit Step Default Description
Operation
1=on
1=on Operation Off / On
Table continues on the next page
1MRS758755 C Measurement functions
REC615 & RER615
Technical Manual