15 Protection relay and functionality tests
15.1 Electromagnetic compatibility tests
Table 767: Electromagnetic compatibility tests
Description Type test value Reference
1 MHz/100 kHz burst disturb-
ance test
IEC 61000-4-18
IEC 60255-26
IEEE C37.90.1-2012
•Common mode 2.5 kV
•Differential mode 2.5 kV
3 MHz, 10 MHz and 30 MHz
burst disturbance test
IEC 61000-4-18
IEC 60255-26
•Common mode 2.5 kV
Electrostatic discharge test IEC 61000-4-2
IEC 60255-26
IEEE C37.90.3-2001
•Contact discharge 8 kV
•Air discharge 15 kV
Radio frequency interference
test
10 V (rms) IEC 61000-4-6
f = 150 kHz...80 MHz IEC 60255-26
10 V/m (rms) IEC 61000-4-3
f = 80...2700 MHz IEC 60255-26
10 V/m ENV 50204
f = 900 MHz IEC 60255-26
20 V/m (rms) IEEE C37.90.2-2004
f = 80...1000 MHz
Table continues on the next page