4.7.6 Signals
Table 503: MAPGAPC Input signals
Name Type Default Description
AI_VALUE FLOAT32 0.0 Analogue input value
BLOCK BOOLEAN 0=False Block signal for acti-
vating the blocking
mode
ENA_ADD BOOLEAN 0=False Enable start added
Table 504: MAPGAPC Output signals
Name Type Description
OPERATE BOOLEAN Operate
START BOOLEAN Start
4.7.7 Settings
4.7.7.1 MAPGAPC Group settings
Table 505: MAPGAPC Group settings (Basic)
Parameter
Values (Range) Unit Step Default Description
Start value -10000.0...10000.0 0.1 0.0 Start value
Start value Add -100.0...100.0 0.1 0.0 Start value Add
Operate delay time 0...200000 ms 100 0 Operate delay time
Table 506: MAPGAPC Non group settings (Basic)
Parameter
Values (Range) Unit Step Default Description
Operation
1=on
5=off
1=on Operation Off / On
Operation mode
1=Over
2=Under
1=Over Operation mode
Table 507: MAPGAPC Non group settings (Advanced)
Parameter
Values (Range) Unit Step Default Description
Reset delay time 0...60000 ms 100 0 Reset delay time
Absolute hysteresis 0.01...100.00 0.01 0.10 Absolute hysteresis
for operation
4.7.8 Monitored data
Protection functions
1MRS758755 C
474 REC615 & RER615
Technical Manual