Fault indication Fault code Additional information
Internal Fault
Card error,X130
76 Card in slot X130 is faulty.
Internal Fault
LHMI module
79 LHMI module is faulty. The fault indication
may not be seen on the LHMI during the
fault.
Internal Fault
RAM error
80 Error in the RAM memory on the CPU card.
Internal Fault
ROM error
81 Error in the ROM memory on the CPU card.
Internal Fault
EEPROM error
82 Error in the EEPROM memory on the CPU
card.
Internal Fault
FPGA error
83 Error in the FPGA on the CPU card.
Internal Fault
RTC error
84 Error in the RTC on the CPU card.
Internal Fault
RTD card error,X130
96 RTD card located in slot X130 may have per-
manent fault. Temporary error has occurred
too many times within a short time.
Internal Fault
COM card error
116 Error in the COM card.
For further information on internal fault indications, see the operation manual.
3.2.2 Warnings
In case of a warning, the protection relay continues to operate except for those
protection functions possibly affected by the fault, and the green Ready LED
remains lit as during normal operation.
Warnings are indicated with the text Warning additionally provided with the name
of the warning, a numeric code and the date and time on the LHMI. The warning
indication message can be manually cleared.
If a warning appears, record the name and code so that it can be
provided to ABB customer service.
Table 26: Warning indications and codes
Warning indication Warning code Additional information
Warning
10 A watchdog reset has occurred.
Table continues on the next page