Fault indication Fault code Additional information
Internal Fault
SO-relay(s),X120
45 Faulty Signal Output relay(s) in card located
in slot X120.
Internal Fault
SO-relay(s),X130
46 Faulty Signal Output relay(s) in card located
in slot X130.
Internal Fault
PO-relay(s),X100
53 Faulty Power Output relay(s) in card located
in slot X100.
Internal Fault
PO-relay(s),X110
54 Faulty Power Output relay(s) in card located
in slot X110.
Internal Fault
PO-relay(s),X120
55 Faulty Power Output relay(s) in card located
in slot X120.
Internal Fault
PO-relay(s),X130
56 Faulty Power Output relay(s) in card located
in slot X130.
Internal Fault
Light sensor error
57 Faulty ARC light sensor input(s).
Internal Fault
Conf. error,X000
62 Card in slot X000 is wrong type, is missing,
does not belong to original configuration or
card firmware is faulty.
Internal Fault
Conf. error,X100
63 Card in slot X100 is wrong type or does not
belong to the original composition.
Internal Fault
Conf. error,X110
64 Card in slot X110 is wrong type, is missing
or does not belong to the original composi-
tion.
Internal Fault
Conf. error,X120
65 Card in slot X120 is wrong type, is missing
or does not belong to the original composi-
tion.
Internal Fault
Conf.error,X130
66 Card in slot X130 is wrong type, is missing
or does not belong to the original composi-
tion.
Internal Fault
Card error,X000
72 Card in slot X000 is faulty.
Internal Fault
Card error,X100
73 Card in slot X100 is faulty.
Internal Fault
Card error,X110
74 Card in slot X110 is faulty.
Internal Fault
Card error,X120
75 Card in slot X120 is faulty.
Table continues on the next page
1MRS758755 C Basic functions
REC615 & RER615
Technical Manual
59