Loading...
9.2.6.4 ESSXSWI Output signals
Table 664: ESSXSWI Output signals
Name Type Description
OPENPOS BOOLEAN Apparatus open position
CLOSEPOS BOOLEAN Apparatus closed position
OKPOS BOOLEAN Apparatus position is ok
9.2.7 Settings
9.2.7.1 DCSXSWI Non group settings
Table 665: DCSXSWI Non group settings (Basic)
Parameter Values (Range) Unit Step Default Description
Identification DCSXSWI1 switch
position
Control Object
identification
Table 666: DCSXSWI Non group settings (Advanced)
Parameter Values (Range) Unit Step Default Description
Event delay 0...60000 ms 1 30000 Event delay of the
intermediate posi-
tion
Vendor 0 External equipment
vendor
Serial number 0 External equipment
serial number
Model 0 External equipment
model
9.2.7.2 ESSXSWI Non group settings
Table 667: ESSXSWI Non group settings (Basic)
Parameter Values (Range) Unit Step Default Description
Identification ESSXSWI1 switch
position
Control Object
identification
Table 668: ESSXSWI Non group settings (Advanced)
Parameter Values (Range) Unit Step Default Description
Event delay 0...60000 ms 1 30000 Event delay of the
intermediate posi-
tion
Vendor 0 External equipment
vendor
Serial number 0 External equipment
serial number
Model 0 External equipment
model
1MRS758755 C Control functions
REC615 & RER615
Technical Manual
641

Table of Contents

Other manuals for ABB Relion REC615