1 2
3
4
5 5
1 t
0
2 t
1
3 Input signal
4 Filtered input signal
5 Filter time
Figure 24: Binary input filtering
At the beginning, the input signal is at the high state, the short low state is filtered
and no input state change is detected. The low state starting from the time t
0
exceeds the filter time, which means that the change in the input state is detected
and the time tag attached to the input change is t
0
. The high state starting from t
1
is detected and the time tag t
1
is attached.
Each binary input has a filter time parameter
"Input # filter"
, where # is the number
of the binary input of the module in question (for example
"Input 1 filter"
).
Table 51: Input filter parameter values
Parameter Values Default
Input # filter time 5...1000 ms 5 ms
3.11.2 Binary input inversion
The parameter
Input # invert
is used to invert a binary input.
Table 52: Binary input states
Control voltage Input # invert State of binary input
No 0 FALSE (0)
Yes 0 TRUE (1)
No 1 TRUE (1)
Yes 1 FALSE (0)
When a binary input is inverted, the state of the input is TRUE (1) when no control
voltage is applied to its terminals. Accordingly, the input state is FALSE (0) when a
control voltage is applied to the terminals of the binary input.
Basic functions
1MRS758755 C
92 REC615 & RER615
Technical Manual