Parameter Values (Range) Unit Step Default Description
8=L.T. inv.
9=IEC Norm. inv.
10=IEC Very inv.
11=IEC inv.
12=IEC Ext. inv.
13=IEC S.T. inv.
14=IEC L.T. inv.
15=IEC Def. Time
17=Programmable
18=RI type
19=RD type
Directional mode 1=Non-directional
2=Forward
3=Reverse
2=Forward Directional mode
Characteristic an-
gle
-179...180 deg 1 60 Characteristic angle
Max forward angle 0...90 deg 1 80 Maximum phase angle in for-
ward direction
Max reverse angle 0...90 deg 1 80 Maximum phase angle in re-
verse direction
Min forward angle 0...90 deg 1 80 Minimum phase angle in for-
ward direction
Min reverse angle 0...90 deg 1 80 Minimum phase angle in re-
verse direction
Table 274: DPHLPDOC Group settings (Advanced)
Parameter Values (Range) Unit Step Default Description
Type of reset curve 1=Immediate
2=Def time reset
3=Inverse reset
1=Immediate Selection of reset curve type
Voltage Mem time 0...3000 ms 1 40 Voltage memory time
Pol quantity 1=Self pol
4=Neg. seq. volt.
5=Cross pol .
7=Pos. seq. volt.
5=Cross pol Reference quantity used to
determine fault direction
Table 275: DPHLPDOC Non group settings (Basic)
Parameter
Values (Range) Unit Step Default Description
Operation
1=on
5=off
1=on Operation Off / On
Num of start pha-
ses
1=1 out of 3
2=2 out of 3
3=3 out of 3
1=1 out of 3 Number of phases
required for oper-
ate activation
Curve parameter A 0.0086...120.0000 1 28.2000 Parameter A for
customer program-
mable curve
Table continues on the next page