Name Type Values (Range) Unit Description
-1=both
DIR_C Enum
0=unknown
1=forward
2=backward
-1=both
Direction phase
C
ANGLE_A FLOAT32 -180.00...180.00 deg Calculated angle
difference, Phase
A
ANGLE_B FLOAT32 -180.00...180.00 deg Calculated angle
difference, Phase
B
ANGLE_C FLOAT32 -180.00...180.00 deg Calculated angle
difference, Phase
C
VMEM_USED BOOLEAN
0=False
1=True
Voltage memory
in use status
DPHLPDOC Enum
1=on
2=blocked
3=test
4=test/blocked
5=off
Status
Table 283: DPHHPDOC Monitored data
Name Type Values (Range) Unit Description
START_DUR FLOAT32 0.00...100.00 % Ratio of start
time / operate
time
FAULT_DIR Enum 0=unknown
1=forward
2=backward
3=both
Detected fault
direction
DIRECTION Enum 0=unknown
1=forward
2=backward
3=both
Direction infor-
mation
Table continues on the next page