Table 328: EFIPTOC Non group settings (Advanced)
Parameter Values (Range) Unit Step Default Description
Reset delay time 0...60000 ms 1 20 Reset delay time
Io signal Sel 1=Measured Io
2=Calculated Io
1=Measured Io Selection for used
Io signal
4.2.1.10 Monitored data
Table 329: FEFLPTOC Monitored data
Name Type Values (Range) Unit Description
START_DUR FLOAT32 0.00...100.00 % Ratio of start
time / operate
time
FEFLPTOC Enum 1=on
2=blocked
3=test
4=test/blocked
5=off
Status
Table 330: EFLPTOC Monitored data
Name Type Values (Range) Unit Description
START_DUR FLOAT32 0.00...100.00 % Ratio of start
time / operate
time
EFLPTOC Enum 1=on
2=blocked
3=test
4=test/blocked
5=off
Status
Table 331: EFHPTOC Monitored data
Name Type Values (Range) Unit Description
START_DUR FLOAT32 0.00...100.00 % Ratio of start
time / operate
time
EFHPTOC Enum 1=on
2=blocked
3=test
Status
1MRS758755 C Protection functions
REC615 & RER615
Technical Manual
291