EasyManua.ls Logo

ABB Relion REC615 - Page 373

ABB Relion REC615
869 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Analogue
GOOSE
receive
Analogue
GOOSE
receive
Analogue
GOOSE
receive
MAX
Analogue
GOOSE
send
HAEFPTOC
I_REF_RES
BLOCK
START
OPERATE
Io
I_HARM_RES
BLKD_I_REF
Figure 185: Protection scheme based on the analog GOOSE communication with
three analog GOOSE receivers
4.2.5.6 Signals
Table 388: HAEFPTOC Input signals
Name Type Default Description
Io SIGNAL 0 Residual current
BLOCK BOOLEAN 0=False Block signal for acti-
vating the blocking
mode
I_REF_RES FLOAT32 0.0 Reference current
Table 389: HAEFPTOC Output signals
Name Type Description
OPERATE BOOLEAN Operate
START BOOLEAN Start
4.2.5.7 Settings
1MRS758755 C
Protection functions
REC615 & RER615
Technical Manual
373

Table of Contents

Other manuals for ABB Relion REC615

Related product manuals