EasyManua.ls Logo

ABB Relion REC615 - Page 422

ABB Relion REC615
869 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Timer
Once activated, the Timer activates the START output. Depending on the value of
the set
Operating curve type
, the time characteristics are selected according to DT
or IDMT.
For a detailed description of the voltage IDMT curves, see
Chapter 11.3.1
IDMT curves for overvoltage protection
in this manual.
When the operation timer has reached the value set by
Operate delay time
in the DT
mode or the maximum value defined by the IDMT, the OPERATE output is activated.
When the user-programmable IDMT curve is selected, the operate time
characteristics are defined by the parameters
Curve parameter A
,
Curve parameter
B
,
Curve parameter C
,
Curve parameter D
and
Curve parameter E
.
If a drop-off situation occurs, that is, a fault suddenly disappears before the operate
delay is exceeded, the reset state is activated. The behavior in the drop-off situation
depends on the selected operate time characteristics. If the DT characteristics are
selected, the reset timer runs until the set
Reset delay time
value is exceeded. If
the drop-off situation exceeds the set
Reset delay time
, the Timer is reset and the
START output is deactivated.
When the IDMT operate time curve is selected, the functionality of the Timer in the
drop-off state depends on the combination of the
Type of reset curve
,
Type of time
reset
and
Reset delay time
settings.
Table 429: Reset time functionality when IDMT operation time curve selected
Reset functionality Setting Type of
reset curve
Setting Type of
time reset
Setting Reset
delay time
Instantaneous
reset
Operation timer
is “Reset instan-
taneously” when
drop-off occurs
“Immediate” Setting has no
effect
Setting has no
effect
Frozen timer Operation timer
is frozen during
drop-off
“Def time reset” “Freeze Op tim-
er
Operate timer is
reset after the
set
Reset delay
time
has elapsed
Linear decrease Operation timer
value linearly de-
creases during
the drop-off sit-
uation
“Def time reset” “Decrease Op
timer”
Operate timer is
reset after the
set
Reset delay
time
has elapsed
Protection functions 1MRS758755 C
422 REC615 & RER615
Technical Manual

Table of Contents

Other manuals for ABB Relion REC615

Related product manuals