EasyManua.ls Logo

ABB Relion REC615 - Page 454

ABB Relion REC615
869 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
4.5.1.6 Signals
Table 478: FRPFRQ Input signals
Name Type Default Description
F SIGNAL 0 Measured frequency
dF/dt SIGNAL 0 Rate of change of fre-
quency
BLOCK BOOLEAN 0=False Block signal for acti-
vating the blocking
mode
Table 479: FRPFRQ Output signals
Name Type Description
OPERATE BOOLEAN Operate
OPR_OFRQ BOOLEAN Operate signal for overfre-
quency
OPR_UFRQ BOOLEAN Operate signal for underfre-
quency
OPR_FRG BOOLEAN Operate signal for frequency
gradient
START BOOLEAN Start
ST_OFRQ BOOLEAN Start signal for overfrequency
ST_UFRQ BOOLEAN Start signal for underfre-
quency
ST_FRG BOOLEAN Start signal for frequency
gradient
4.5.1.7 Settings
FRPFRQ Group settings
Table 480: FRPFRQ Group settings (Basic)
Parameter
Values (Range) Unit Step Default Description
Operation mode
1=Freq<
2=Freq>
3=df/dt
4=Freq< + df/dt
5=Freq> + df/dt
6=Freq< OR df/dt
7=Freq> OR df/dt
1=Freq< Frequency protec-
tion operation
mode selection
Start value Freq> 0.9000...1.2000 xFn 0.0001 1.0500 Frequency start val-
ue overfrequency
Start value Freq< 0.8000...1.1000 xFn 0.0001 0.9500 Frequency start val-
ue underfrequency
Start value df/dt -0.2000...0.2000 xFn /s 0.0001 0.0100 Frequency start val-
ue rate of change
Table continues on the next page
Protection functions 1MRS758755 C
454 REC615 & RER615
Technical Manual

Table of Contents

Other manuals for ABB Relion REC615

Related product manuals