The retrip logic is inactive if the
CB fail retrip mode
setting is set to "Off".
If
CB fail retrip mode
is set to the "Current check" mode, the activation of the
retrip output TRRET depends on the
CB failure mode
setting.
- If
CB failure mode
is set to the "Current" mode, TRRET is activated when
the value of any phase current exceeds the
Current value
setting. The TRRET
output remains active for the time set with the
Trip pulse time
setting or until
all phase current values drop below the
Current value
setting, whichever is
longer.
- If
CB failure mode
is set to the "Breaker status" mode, TRRET is activated if
the circuit breaker is in the closed position. The TRRET output remains active
for the time set with the
Trip pulse time
setting or the time the circuit breaker
is in the closed position, whichever is longer.
- If
CB failure mode
is set to "Both", TRRET is activated when either of the
"Breaker status" or "Current" mode condition is satisfied.
If
CB fail retrip mode
is set to the "Without check" mode, TRRET is activated once
the timer 1 is activated without checking the current level. The TRRET output
remains active for a fixed time set with the
Trip pulse time
setting.
The activation of the BLOCK input or the CB_FAULT_AL output deactivates the
TRRET output.
POSCLOSE
I >
From Level detector 1
Timer 1 elapsed
From Timer 1
OR
AND
AND
CB fail retrip mode
”Without check”
CB fail retrip mode
”Current check”
CB failure mode ”Current”
CB failure mode ”Breaker
status
CB failure mode ”Both”
AND
AND
AND
OR
OR
AND
TRRET
BLOCK
CB_FAULT_AL
From Timer 3
Figure 240: Retrip logic
Backup trip logic
The backup trip logic provides the TRBU output which can be used to trip the
upstream backup circuit breaker when the main circuit breaker fails to clear the
fault. The backup trip logic is activated by the timer 2 module or timer-enabling
signal from the start logic module (rising edge of the START input detected), and
simultaneously CB_FAULT_AL is active. The operation of the backup logic depends
on the
CB failure mode
setting.
If the
CB failure mode
is set to "Current", the activation of TRBU depends on the
CB failure trip mode
setting.
- If
CB failure trip mode
is set to "1 out of 3", the failure detection is based on
any of the phase currents exceeding the
Current value
setting. Once TRBU is
1MRS758755 C
Protection related functions
REC615 & RER615
Technical Manual
485