Parameter Values (Range) Unit Step Default Description
min and max as
0,001 % s)
Table 596: VMMXU Non group settings (Advanced)
Parameter Values (Range) Unit Step Default Description
Measurement
mode
1=RMS
2=DFT
2=DFT Selects used meas-
urement mode
8.1.5.5 Monitored data
VMMXU Monitored data
Table 597: VMMXU Monitored data
Name Type Values (Range) Unit Description
U12-kV FLOAT32 0.00...4.00 xUn Measured phase
to phase voltage
amplitude phase
AB
U23-kV FLOAT32 0.00...4.00 xUn Measured phase
to phase voltage
amplitude phase
BC
U31-kV FLOAT32 0.00...4.00 xUn Measured phase
to phase voltage
amplitude phase
CA
BLOCK BOOLEAN
0=False
1=True
Block signal for
all binary out-
puts
HIGH_ALARM BOOLEAN
0=False
1=True
High alarm
HIGH_WARN BOOLEAN
0=False
1=True
High warning
LOW_WARN BOOLEAN
0=False
1=True
Low warning
LOW_ALARM BOOLEAN
0=False
1=True
Low alarm
U_INST_AB FLOAT32 0.00...4.00 xUn U12 Amplitude,
magnitude of in-
stantaneous val-
ue
Table continues on the next page
Measurement functions 1MRS758755 C
584 REC615 & RER615
Technical Manual