Table 31: Non group settings
Parameter Values (Range) Unit Step Default Description
Synch source 0=None
1=SNTP
2=Modbus
3=IEEE 1588
5=IRIG-B
9=DNP
17=IEC60870-5-10-3
1=SNTP Time synchronization
source
PTP domain ID 0...255 1 0 The domain is identi-
fied by an integer, the
domainNumber, in the
range of 0 to 255.
PTP priority 1 0...255 1 128 PTP priority 1, in the
range of 0 to 255.
PTP priority 2 0...255 1 128 PTP priority 2, in the
range of 0 to 255.
PTP announce
mode
1=Basic IEEE1588
2=Power Profile
1=Basic IEEE1588 PTP announce frame
mode
Table 32: Non group settings
Parameter Values (Range) Unit Step Default Description
Date 0 Date
Time 0 Time
Local time offset -840...840 min 1 0 Local time offset in mi-
nutes
Table 33: Non group settings
Parameter Values (Range) Unit Step Default Description
IP SNTP primary 10.58.125.165 IP address for SNTP primary
server
IP SNTP secondary 192.168.2.165 IP address for SNTP secon-
dary server
Table 34: Non group settings
Parameter Values (Range) Unit Step Default Description
DST in use 0=False
1=True
1=True DST in use setting
DST on time
(hours)
0...23 h 2 Daylight saving time on, time
(hh)
DST on time (mi-
nutes)
0...59 min 0 Daylight saving time on, time
(mm)
DST on date (day) 1...31 1 Daylight saving time on, date
(dd:mm)
DST on date
(month)
1=January
2=February
3=March
5=May Daylight saving time on, date
(dd:mm)
Table continues on the next page
Basic functions 1MRS758755 C
72 REC615 & RER615
Technical Manual