100 SensyMaster FMT430, FMT450 THERMAL MASS FLOWMETER | OI/FMT430/450-EN REV. B
9 Operation
Parameter descriptions
Menu / parameter
Description
Easy Setup
Binary Out 51/52
Selection of binary
output function.
Alarm: The binary output indicates an active alarm. The alarm is selected in the ‘„...Alarm Cfg. 51/52’ menu.
Batch End: The binary output is activated when the set fill quantity is reached (only if the FillMass function is activated).
Dig.Out V1/V2 Mode
Selection of the operating mode for digital output V1 / V2.
Digital output V1 / V2 is only available if the corresponding plug
-in card is present!
Off: Digital output V1 / V2 deactivated.
Binary: Digital output V1 / V2 as a binary output (for example, as an alarm output).
Binary Out V1/V2
Selection of binary output function.
Alarm: The binary output indicates an active alarm. The alarm is selected in the ‘„...Alarm Cfg. 51/52’ menu.
Batch End: The binary output is activated when the set fill quantity is reached (only if the FillMass function is activated).
Dig.Out V3/V4 Mode
Selection of the operating mode for digital output V3 / V4.
Digital output V3 / V4 is only available if the corresponding plug
-in card is present!
Off: Digital output V3 / V4 deactivated.
Binary: Digital output V3 / V4 as a binary output (for example, as an alarm output).
Binary Out V3/V4
Selection of binary output function.
Alarm: The binary output indicates an active alarm. The alarm is selected in the ‘„...Alarm Cfg. 51/52’ menu.
Batch End: The binary output is activated when the set fill quantity is reached (only if the FillMass function is activated).
Application
Application selection (type of measuring medium)
Air: Using the device with factory calibration for air.
Application 1 ... 8: Selection of the appropriate application. The individual applications are configured in the ‘Device
Setup / ...Sensor / ...Application 1 ... 8’ menu.
Dig.In 0 Application
Dig.In 1 Applic
ation
Dig.In 2 Application
Dig.In1+2Application
Use of optional digital inputs for application switching. You can switch between four applications by wiring the digital
inputs.
Dig.In 0 Application: Assignment of the application if no digital inputs are active.
Dig.In 1 Application: Assignment of the application if only digital input V1 / V2 is active.
Dig.In 2 Application: Assignment of the application if only digital input V3 / V4 is active.
Dig.In1+2Application: Assignment of the application if only digital input V1 / V2 and V3 / V4 are active.
Note
The function is available only with the corresponding plug
-in cards in place! The digital inputs must be configured in the
Input/Output / ...Dig.In V1/V2” or “Input/Output / ...Dig.In V1/V2” menu using the “Act. App.Selector1|3function or “Act.
App.Selector2|3 function.