SensyMaster FMT430, FMT450 THERMAL MASS FLOWMETER | OI/FMT430/450-EN REV. B 117
Menu / parameter
Description
Input/Output /
...Dig.Out V1/V2
Input/Output / ...Dig.Out V3/V4
Mode
Selection of operating mode for the digital output V1
/ V2 or V3 / V4.
Off: Digital output deactivated.
Binary: Digital output functions as binary output (for function see parameter ‘„...Binary Out V1/V2 / V3/V4’).
The digital outputs V1 / V2 and V3 / V4 are only available if the corresponding plug-in cards are present!
...Binary Out V1/V2 / V3/V4
Selection of submenu ‘
...Binary Out V1/V2 / V3/V4’ using .
Only available if ‘Mode’ Binary has been selected.
...Alarm Cfg. V1/V2 / V3/V4
Selection of submenu ‘
...Alarm Cfg. V1/V2 / V3/V4’ using .
Only available if ‘Mode’ Binary has been selected.
Input/Output / ...Dig.Out V1/V2 /
...Binary Out V1/V2
Input/Output / ...Dig.Out V3/V4 /
...Binary Out V3/V4
Signal Source Binary
Selection of binary output function.
See description ‘„Input/Output / ...Dig.Out 41/42 / ...Binary Out 41/42’.
Active Mode
Select switching properties for the binary output.
Active High: Normally open
Active Low: Normally closed
Input/Output / ...Dig.Out V1/V2 /
...Alarm Cfg. V1/V2
Input/Output / ...Dig.Out V3/V4 / ...Alarm Cfg. V3/V4
General Alarm
Select error messages signaled via the binary output V1
/ V2 or V3 / V4.
Only if the parameter "
Signal Source Binary" has been set to “Alarm“.
Qm Massflow Max
Qm Massflow Min
Qv@ Volumeflow Max
Qv@ Volumeflow Min
Tm Temperature Max
Tm Temperature Min
Sensor Soiling
In preparation
Input/Output /
...Dig.In V1/V2
Input/Output / ...Dig.In V3/V4
Function
Select a
function for the digital input.
Off: No function.
Reset all Totalizer: Counter reset for all counters
Stop all Totalizer: External counter stop for all counters
Set Flowrate to zero: Sets flow measurement to 0. Heating of the thermal measuring element is also switched off here
Start/Stop Batching: Start / stop fill operation (only when FillMass function is activated).
Act. App.Selector1|3: Application selection via the digital input (with digital input V1 / V2 only).
Act. App.Selector2|3: Application selection via the digital input (with digital input V3 / V4 only).
Active Mode
Select switching properties for the digital input.
Active High: Normally open
Active Low: Normally closed
Delay Time
Selection of delay time for
suppressing EMC faults on the digital input.