184 Rockwell Automation Publication 1756-UM535D-EN-P - November 2012
Chapter 7 Program the Redundant Controller
Use this table to determine the Retain Test Edits on Switchover setting that suits
your application.
To change the Retain Test Edits on Switchover setting, click the Redundancy tab
in the Controller Properties then click Advanced.
Figure 56 - Retain Test Edits on Switchover
If you need to Then
Prevent a test edit from faulting both the primary and secondary
controller
Leave Retain Test Edits on Switchover
unchecked
Keep test edits active, even in the event of a switchover and at the risk
of faulting both controllers
Check Retain Test Edits on Switchover