EasyManua.ls Logo

Allen-Bradley 1756-RM2 - Appendix D; Replace Local IO Tags

Allen-Bradley 1756-RM2
296 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
268 Rockwell Automation Publication 1756-UM535D-EN-P - November 2012
Appendix D Convert from a Nonredundant System
Replace Local I/O Tags
If you have moved I/O modules out of the local controller chassis and into the
remote I/O chassis, complete these steps to find and replace the local I/O tags in
your program.
1. Open the routine where the local I/O tags need to be updated.
2. Press CTRL+H to open the Replace in Routines dialog box.
3. From the Find What pull-down menu, choose Local:.
4. From the Replace With pull-down menu, choose the name of the
communication module where the remote I/O was placed.
5. From the Find Where pull-down menu, choose All Routines.
6. Click Find Within >>.
7. Select Ladder Diagrams.
8. Check Instruction Operands.

Table of Contents

Related product manuals