EasyManua.ls Logo

Allen-Bradley 1756-RM2 - Use RSLogix 5000 Software to View Errors

Allen-Bradley 1756-RM2
296 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Rockwell Automation Publication 1756-UM535D-EN-P - November 2012 201
Troubleshoot a Redundant System Chapter 9
Use RSLogix 5000 Software
to View Errors
To view redundancy status by using RSLogix 5000 software, complete these
steps.
1. Go online with the redundant controller.
2. Either click Primary or Secondary, depending on the controller you are
online with.
The redundant controller ID and status are displayed.
Primary
Controller
Secondary
Controller

Table of Contents

Related product manuals