Rockwell Automation Publication 1766-UM001I-EN-P - June 2015 165
Specifications Appendix A
Continuous current per
common, max.
8A 8A 7A (Also seeRelay
Contact Ratings” on
page 157.)
8A
Continuous current per
module, max.
16 A 16 A 30A (Also see Module
Load Ratings
1762-OX6I on page
166.)
8A
Surge current, max. See “Relay Contact Ratings” on page 165. See “Relay Contact
Ratings” on page 165.
See “Relay Contact
Ratings” on page 165.
Isolated groups Group 1: Outputs 0 to
3
Group 2: Outputs 4 to
7
Group 1: Outputs 0 to
7
Group 2: Outputs 8 to
15
All 6 Outputs
Individually Isolated.
Group 3:
Outputs 0 to 5
Output group to
backplane isolation
Verified by one of the following dielectric tests: 1836V AC for 1 s or 2596V DC for 1 s.
265V AC working voltage (IEC Class 2 reinforced insulation)
Output group to output
group isolation
Verified by one of the following dielectric tests: 1836V AC for 1 s or 2596V DC for 1 s.
265V AC working voltage (basic insulation)
150V AC working voltage (IEC Class 2 reinforced insulation)
Vendor I.D. code 1
Product type code 7
Product code 1
20
1
21
124 98
(1) Only applicable to Series B I/O modules.
Output Specifications
Specification 1762-OW8 1762-OW16 1762-OX6I 1762-IQ8OW6
Relay Contact Ratings (1762-OW8, 1762-OW16, and 1762-IQ8OW6)
Maximum Volts Amperes
Continuous
Amperes Volt-Amperes
Make Break Make Break
240V AC 2.5A
(1)
(1) 1.5A above 40 °C (104 °F).
7.5A 0.75A 1800 VA 180 VA
120V AC 2.5A
(1)
15A 1.5A 1800 VA 180 VA
125V DC 1.0A 0.22A
(2)
(2) For DC voltage applications, the make/break ampere rating for relay contacts can be determined by dividing 28
VA by the applied DC voltage. For example, 28 VA/48V DC = 0.58A. For DC voltage applications less than 14V,
the make/break ratings for relay contacts cannot exceed 2A.
28 VA
24V DC 2.0A 1.2A
(2)
Relay Contact Ratings 1762-OX6I
Volts (max.) Continuous
Amps per
Point
(max.)
(1)
Amperes
(3)
Voltamperes
Make Break Make Break
240V AC 5.0 A 15 A 1.5 A 3600 VA 360 VA
120V AC 7.0 A
(2)
30 A 3.0 A
125V DC 2.5 A 0.4 A 50 VA
(4)
24V DC 7.0 A
(2)
7.0 A 168 VA
(4)

Table of Contents