The SLC 5/03 processor offers the following:
program memory size of 8K or 16K
control of up to 4096 input and output points
online programming (includes runtime editing)
built-in DH-485 channel
built-in RS-232 channel, supporting:
DF1 Full-Duplex for point-to-point communication; remotely
via a modem, or direct connection to programming or operator
interface devices. (Use a 1747-CP3 cable for direct
connection.)
DF1 Half-Duplex Master/Slave for SCADA type
(point-to-multipoint) communication
DH-485 (Serves as a second DH-485 channel. Use a
1761-NET-AIC with a 1747-CP3 cable to connect to the
DH-485 network.)
ASCII I/O for connection to other ASCII devices, such as bar
code readers, serial printers, and weigh scales
remote I/O passthru
built-in real-time clock/calendar
2 ms Selectable Timed Interrupt (STI)
0.50 ms Discrete Input Interrupt (DII)
advanced math features – trigonometric, PID, exponential,
floating point, and the compute instruction
indirect addressing
flash PROM provides firmware upgrades without physically
changing EPROMS
optional flash EPROM memory module available
keyswitch – RUN, REMote, PROGram (clear faults)
battery-backed RAM
additional instructions such as swap and scale with parameters
(SLC 5/03 OS302 processor or higher)
multi-point list (SLC 5/03 OS302 processor or higher)
UL listed, CSA approved, CE compliant