Publication 1752-UM001A-EN-P - October 2006
Explicit Messages 213
Setting and Monitoring Safety Input Terminals
Explicit
Message
Service Function
Command
Response
Service
Code
Class
ID
Instance
ID
Attribute
ID
Data Size
Monitor
Mode for
Terminal
Maintenance
Information
Read Reads the monitor
mode of
maintenance
information for the
input (1…16)
specified by the
Instance ID.
0E hex 3D hex 01 to 10
hex
65 hex
1 byte
00 hex: Total On
Time mode
01 hex: Contact
Operation Counter
mode
Write Writes the monitor
mode of
maintenance
information for the
input (1…16)
specified by the
Instance ID.
10 hex 3D hex 01 to 10
hex
65 hex 1 byte
00 hex: Total On
Time mode
01 hex: Contact
Operation Counter
mode
SV for Input
Total On Time
or Contact
Operation
Counter
Read Reads the SV of the
total on time or
contact operation
counter for the input
(1…16) specified by
the Instance ID.
0E hex 3D hex 01 to 10
hex
68 hex
4 bytes
0000 0000 …
FFFF FFFF hex
(0…4,294,967,295)
Write Writes the SV of the
total on time or
contact operation
counter for the input
(1…16) specified by
the Instance ID.
10 hex 3D hex 01 to 10
hex
68 hex 4 bytes
0000 0000…
FFFF FFFF hex
(0…4,294,967,295)
Read Input
Total On Time
or Contact
Operation
Counter
Read Reads the total on
time or contact
operation counter for
the input (1…16)
specified by the
Instance ID.
0E hex 3D hex 01 to 10
hex
66 hex
4 bytes
0000 0000 …
FFFF FFFF hex
(0…4,294,967,295)
Reset Input
Total On Time
or Contact
Operation
Counter
Reset Resets to 0 the total
on time or contact
operation counter for
the input (1…16)
specified by the
Instance ID.
05 hex 3D hex 01 to 10
hex
66 hex
——
Read Monitor
Status of
Input Total
On Time or
Contact
Operation
Counter
Read Reads the monitor
status of the total on
time or contact
operation counter for
the input (1…16)
specified by the
Instance ID.
0E hex 3D hex 01 to 10
hex
67 hex
1 byte
00 hex: in range
01 hex: out of range
(over monitor value)

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Allen-Bradley SmartGuard 600 and is the answer not in the manual?

Allen-Bradley SmartGuard 600 Specifications

General IconGeneral
BrandAllen-Bradley
ModelSmartGuard 600
CategoryController
LanguageEnglish

Related product manuals