Rockwell Automation Publication 1560F-UM001A-EN-P - June 2019 151
Diagnostics Chapter 8
Table provides an overview of the Fault and Alarm codes with Time Delay and
Restart options plus a basic description of what causes each Fault or Alarm to
occur.
NVS Error 34 5 D Clear Fault
(3)
75
V24 Recovery 35 5 D X Fault
(3)
76
V24 Loss 36 5 D X Param Change
(3)
77
VControl Loss 37 5 D X Reserved 78-99
TB Input
(1)
1 38 6 D X X System Faults 100-199 5 D X
239 X X
3 40 ——X
4 41 ——X
Current Imbal 42 7 M X
(1) TB = Terminal Block Input
(2) For Category, M= Motor; D=Device
(3) Codes 71...77 are Event codes.
TIP Most Faults and Alarms are individually bit enabled and disabled (F/A Bit
Enab) and can have a user configurable delay time to help avoid nuisance
trips (Time Delay Aval). In addition, many have the ability to automatically
restart once the condition is cleared (Restart En).
Table 57 - Linear Listing—Fault and Alarm Code Overview
Fault/Alarm
Code Name
F/A Code
Time Delay Avail.
F/A Bit Enable
Restart Enable
Description
F/A= Fault and Alarm, A= Alarm, F= Fault
Line Loss A 1 N Y Y F/A Loss of line power for Phase A, B, or C
B2
C3
Shorted SCR A 4 N N N
A
A During prestart checks
(motor stopped not
running), the SMC-50
control module monitors
for current flow in each
individual phase.
NOTE: In Wye configurations, a single
Phase A, B, or C shorted SCR is not
detected until the unit is started. This
fault is always enabled.
B5
C6
Open Gate A 7 N Y Y F/A Indicates that an abnormal condition that causes faulty firing (for
example, open SCR Gate) has been sensed during the starting
sequence.
B8
C9
SCR Overtemp 10 NNN
A
F The SMC-50 control module protects the SCRs from damage caused
by overtemperature operation using an internally configured I
2
t. NOTE:
This fault is always enabled.
Table 56 - Fault/Alarm Code Cross-Reference (Continued)
Fault/Alarm
Name
Code
LED Code
Category
(2)
Host
DPI/HIM/COMM
Exp 7, 8, 9
Fault/Alarm Name
Code
LED Code
Category
(2)
Host
DPI/HIM/COMM
Exp 7, 8, 9