EasyManuals Logo

Allen-Bradley SMC-50 User Manual

Allen-Bradley SMC-50
292 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #98 background imageLoading...
Page #98 background image
98 Rockwell Automation Publication 1560F-UM001A-EN-P - June 2019
Chapter 4 Programming
Input 1 Programs the desired operation of the Control Module to a change in status of Input #1 wired to
control terminal #11 (24V DC).
Disable, Start, Coast, Stop Option, Start/
Coast, Start/Stop, Dual Ramp, OL
Select, Fault, Fault NC, Clear Fault,
Emerg Run
Start/Coast
Input 2 Programs the desired operation of the Control Module to a change in status of Input #2 wired to
control terminal #10 (24V DC).
Disable
Aux 1 Config Aux 1 Config Programs the control function of the Auxiliary Output Contact #1, wired across control
terminal #4 and #5.
(4)
Normal, UTS, Fault, Alarm, Ext Bypass,
Ext Brake, Aux Control
(7)
, Network 1,
Network 2, Network 3, Network 4,
Fan Control
Normal
Aux 2 Config Programs the control function of the Auxiliary Output Contact #2, wired across control terminal #6
and #7.
(4)
Overload Class Required for motor protection. Lets you select the time-to-trip for the built-in Motor Overload.
This selection is based on the type of motor being used and the application it is being applied to.
5…30 10
Service Factor Required for motor protection. This value is taken directly from the nameplate and used by the
controller to determine the ultimate Overload Trip Current.
0.01...1.99 1.15
Motor FLC Required for motor protection. This programmed value is taken directly from the motor
nameplate.
1.0...2200.0 A 1.0 A
Starting Torque NOT used for a Soft Start. 0...300% RMT 100% RMT
Max Torque NOT used for a Soft Start. 0...300% RMT 250% RMT
Rated Torque NOT used for a Soft Start. 0...100,000 N•m 10 N•m
Rated Speed NOT used for a Soft Start. 750, 900, 1000, 1200, 1500, 1800,
3500, 3600 rpm
1800 rpm
(1) In the AUTO Detect [default] selection, the controller automatically checks the motor configuration.
(2) Enter a value to limit the current but not low enough to inhibit the start cycle.
(3) The stopping mode does not need to match the starting mode (for example, a Soft Start can have a stop mode programmed for [Coast], or Linear Stop—there is no Current Limit Stop or Torque Stop
mode).
(4) Relay Operational Options (for example, ON and OFF delay, etc.) are provided in the File: Setup, Group: I/O selection sequence. See Ta ble 1 1
.
(5) Kickstart is available when using Soft Start. A Kickstart Level and Time must be configured if this mode is used. Access these parameters via the Starting Setup Group. The Starting Setup Group can be
accessed with the HIM from the Port <00> DEV PARAM folder under the File-Group, File: Setup, Group: Starting selection sequence (see Table 11
). Setting either parameter to zero disables Kickstart.
(6) You can also program a start delay time to delay starting for a period of time after the initiation of the START command. The Start Delay parameter can be accessed from the Group Starting selection
as noted.
(7) Any auxiliary output configured for Aux Control using the AuxX Config parameter is under control of its associated bit from the Aux Control, Parameter 180. See Parameter 180 information for bit
assignments.
NOTE: This function enables forcing an output, ON or OFF.
Table 12 - Soft Start Parameter Group (Continued)
Parameter
Name
Description
Options
Default
Value
ATTENTION: For Overload Protection, it is critical that you enter the data into
the SMC-50 control module as it appears on the motor nameplate.

Table of Contents

Other manuals for Allen-Bradley SMC-50

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Allen-Bradley SMC-50 and is the answer not in the manual?

Allen-Bradley SMC-50 Specifications

General IconGeneral
BrandAllen-Bradley
ModelSMC-50
CategoryController
LanguageEnglish

Related product manuals