No.. Display Description Remedy
722
Tempdiff HW
Please call tter
Temperature spread in the heating mode is nega-
tive (=erroneous)
Check function and location of the
ow and return sensor.
723
Tempdiff SW
Please call tter
Temperature spread in the domestic hot water
mode is negative (=erroneous)
Check function and location of the
ow and return sensor.
724
Tempdiff defrosting
Please call tter
Temperature spread in the heating circle is > 15 K
during defrosting (=danger of frost)
Check function and location of the
ow and return sensor, HCP capacity,
overows and heating circles.
725
System error SW
Please call tter
Domestic hot water faulty, desired tank tempera-
ture is fallen below substantially
Check circulating pump HW, tank
lling, shutoff move and 3-way valve.
Ventilate hot water and SW.
726
Sensor mixing circ 1
Please call tter
Break or short-circuit in the mixing circle sensor
Check mixing circle sensor, plug and
connection line.
727
Brine pressure
Please call tter
Brine pressure pressostat has responded during
the pre-rinsing time or during operation
Check brine pressure and brine pres-
sure pressostat.
728
Sensor HS Off
Please call tter
Break or short-circuit in the heat source sensor at
the HS outlet
Check heat source sensor, plug and
connection line.
729
Rotating eld error
Please call tter
Compressor without power after switching on Check rotating eld and compressor.
730
Screed heating error
Please call tter
The screed heating program could not reach an
FL temperature level in the specied time interval.
Screed heating program continues running.
The screed heating program could
not reach an FL temperature level in
the specied time interval. Screed
heating program continues running.
732
Cooling fault
Please call tter
The hot water temperature of 16 °C has been
fallen short of several times
Check mixer and heating circulation
pump.
733
Anode fault
Please call tter
Fault input of the impressed current anode has re-
sponded
Check connection line between
anode and potentio stat. Fill SW tank.
734
Anode fault
Please call tter
Error 733 present for more than two weeks and do-
mestic hot water is locked
Acknowledge error in order to release
domestic hot water preparation again.
Rectify 733.
735
Error Ext. En
Please call tter
Only possible with installed Comfort / expansion
board: Break or short-circuit in the sensor “External
energy source”
Check sensor “External energy
source”, plug and connection line.
736
Error solar collector
Please call tter
Only possible with installed Comfort / expansion
board: Break or short-circuit in the “solar collector”
sensor
Check “solar tank” sensor, plug and
connection line.
737
Error solar tank
Please call tter
Only possible with installed Comfort / expansion
board: Break or short-circuit in the “solar tank”
sensor
Check “solar tank” sensor, plug and
connection line.
738
Error mixing circle 2
Please call tter
Only possible with installed Comfort / expansion
board: Break or short-circuit in the “mixing circle 2”
sensor
Check “mixing circle 2” sensor, plug
and connection line.
750
Return sensor external
Please call tter
Break or short-circuit in the external return sensor
Check external return sensor, plug
and connection line.
751 Phase monitoring fault Phase-sequence relay has responded
Check rotary eld and phase-se-
quence relay.
752 Flow error
Phase-sequence relay or ow switch has re-
sponded
see errors No. 751 and No. 717
755
Lost connection to slave
Please call tter
A slave has not responded for more than 5 min-
utes.
Check network connection, switch,
and IP addresses. Perform HP
search if necessary.
756
Lost connection to master
Please call tter
A master has not responded for more than 5 min-
utes.
Check network connection, switch,
and IP addresses. Perform HP
search if necessary.

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Alpha-InnoTec Luxtronik 2.0 and is the answer not in the manual?

Alpha-InnoTec Luxtronik 2.0 Specifications

General IconGeneral
BrandAlpha-InnoTec
ModelLuxtronik 2.0
CategoryController
LanguageEnglish

Related product manuals