No.. Display Description Remedy
701
Error low pressure.
Please call tter
Low pressure pressostat in the cooling circle has
responded (LW) or for longer than 20 seconds
(SW).
Check HP for leakage, switching
point pressure state, defrosting and
T-outd.min.
702
Low pressure stop
RESET autom.
Only possible for L/W devices: Low pressure in the
cooling circle has responded. After some time, au-
tomated HP restart
Check HP for leakage, switching
point pressure state, defrosting and
T-outd.min.
703
Antifreeze
Please call tter
Only possible for L/W devices: If the heat pump is
running and the temperature in ow is < 5 °C, anti-
freeze is detected
Check HP power, defrost valve and
heating system.
704
Error hot gas
Reset in hh:mm
Maximum temperature in the hot gas cooling circle
exceeded. Automatic HP restart after hh:mm
Check coolant quantity, evaporation,
overheating ow, return and HS-min.
705
Motor protection VEN
Please call tter
Motor protection has responded Check set value and ventilator / BCP.
706
Motor protection BCP
Please call tter
Option only possible for S/W- or W/W devices
Motor protection of the brine or well water circu-
lating pump or the compressor has responded
Check set values, compressor, BOS.
707
Coding of HP
Please call tter
Break or short-circuit of the coding bridge in HP
after the rst switch-on
Coding resistance in HP, check plug
and connection line.
708
Return sensor
Please call tter
Break or short-circuit in the return sensor
Check return sensor, plug and con-
nection line.
709
Flow sensor
Please call tter
Break or short-circuit in the ow sensor No fault
shutdown for S/W- or W/W devices
Check ow sensor, plug and connec-
tion line.
710
Hot gas sensor
Please call tter
Break or short-circuit in the hot gas sensor of the
cooling circle
Check hot gas sensor, plug and con-
nection line.
711
External temp. sensor
Please call tter
Break or short-circuit in the external temperature
sensor No fault shutdown. Fixed value to -5 °C
Check external temperature sensor,
plug and connection line.
712
Domestic hot water sensor.
Please call tter
Break or short-circuit in the domestic hot water
sensor No fault shutdown.
Check domestic hot water sensor,
plug and connection line.
713
HS-on sensor
Please call tter
Break or short-circuit in the heat source sensor
(inlet)
Check heat source sensor, plug and
connection line.
714
Hot gas SW
Reset in hh:mm
Check thermal application limit of the HP. Domestic
hot water off for hh:mm
Check ow of domestic hot water,
heat exchanger, domestic hot water
temperature and circulation pump.
715
High-pressure switch-off
RESET autom.
High pressure in the cooling circle has responded.
After some time, automated HP restart
Check ow of HW, overows, temper-
ature and condensation.
716
High-pressure fault
Please call tter
High pressure pressostat in the cooling circle has
responded several times.
Check ow of HW, overows, temper-
ature and condensation.
717
Flow HS
Please call tter
Flow switch for W/W devices has responded during
the pre-rinsing time or operation
Check ow, switching point for DFS,
lter, air clearance. .
718
Max. outside temp.
RESET autom. in hh:mm
Only possible for L/W devices: Outside tempera-
ture has exceeded permissible maximum value.
Automatic HP restart after hh:mm
Check outside temperature and set
value.
719
Min. outside temp.
RESET autom. in hh:mm
Only possible for L/W devices: Outside temper-
ature has fallen below the permissible minimum
value. Automatic HP restart after hh:mm
Check outside temperature and set
value.
720
HS temperature
RESET autom. in hh:mm
Option only possible for S/W- or W/W devices Tem-
perature at evaporation outlet has fallen below the
safety value on the HS side several times. Auto-
matic HP restart after hh:mm
Check ow, lter, air clearance, tem-
perature.
721
Low-pressure switch-off
RESET autom.
Low pressure pressostat in the cooling circle has
responded. After some time, automated HP restart
(SW and SW)
Check switching point of the pres-
sostat, ow on HS side.
Error Diagnosis / Error messages

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Alpha-InnoTec Luxtronik 2.0 and is the answer not in the manual?

Alpha-InnoTec Luxtronik 2.0 Specifications

General IconGeneral
BrandAlpha-InnoTec
ModelLuxtronik 2.0
CategoryController
LanguageEnglish

Related product manuals