Series 90B ANNUNCIATOR INSTALLATION AND CONFIGURATION MANUAL
i. 93
Alarm Sequence
Sequence Selections
Standard ISA Sequences: A, A4, A4-5-6, M, F1A, F2A, F2M, F3A, F3M,
FFAM2, R, R-12
Dual Color Sequences: F3C, RC, R-12C
Up to 4 Sequences per system
Sequence configured in Software (by input)
Customized flash rates
100 millisecond increments (Selectable in Software)
First Out Groups
Up to 4 first out groups per system
5 millisecond First Out Discrimination
Lamp Synchronization
Synchronize other displays to same flash rate. Master system outputs a pulse at
the slow flash rate. Slaves re-sync to incoming “lamp off” edge. A master system
may drive up to 5 slave units.