Series 90B ANNUNCIATOR INSTALLATION AND CONFIGURATION MANUAL
i. 107
Point Mode
The system can present or accept (transmit or receive) raw field input point data
plus alarm controls. Single and multiple register writes are supported. Data is
again presented in a 16 bit register format. The last word of a transfer of input
data may optionally contain control data.
The data layout for a sample system configured for point data will be as below.
Word
Bit15
.
….
Bit6
Bit5
Bit4
Bit3
Bit2
Bit1
Bit0
1
AP
16
..
..
..
..
..
..
AP
01
..
..
..
..
..
..
..
..
..
15
AP
240
..
..
..
..
..
..
AP
225
16
Ack
Rec
Rst
Rec
Ack
Tran
Rst
Tran
AP refers to Alarm Point Channel. ACK refers to the Acknowledge Pushbutton
and RST refers to the RESET Pushbutton.
The local pushbutton controls (on the front of the Annunciator and other ones
connected to the external pushbutton inputs) can be transmitted (Tran) to a
remote device using Ack Tran and Rst Tran as shown. The Annunciator can
also receive (Rec) the pushbutton controls from the remote device using Ack
Rec and Rst Rec as shown.