Series 90B ANNUNCIATOR INSTALLATION AND CONFIGURATION MANUAL
i. 97
Mechanical
Enclosures: Semi-flush Panel Mount,
19” Rack Mount,
Surface (wall) mount,
NEMA Enclosures
Size: Depends on Annunciator Configuration (# of cells high x wide)
Weight: 1.5 LB per cell (0.8kg per cell)
Connections / terminations
Field Contact Input, Relay Output, Power Input Terminals
-Barrier Terminal Block, #6-32 screw. Accepts Ring, Spade Lug or Bare Wire
-Wire size: 12-22 AWG
Pushbutton/Switch Input, Lamp Synchronization Terminals
-Barrier Terminal Block, #6-32 screw. Accepts Ring, Spade Lug or Bare Wire
-Wire size: 14-22 AWG
Serial Communication Port(s)
9 Pin Female D connector
Ethernet Communication Port
-RJ45 connector
IRIG-B Time Synchronization Input
-BNC connector
Environment
Operating Temperature Range: -20 TO 50
O
C (-4 to 122
o
F)
Storage Temperature Range: -20 TO 80
O
C (-4 to 176
o
F)
Humidity: 20-95% RH