104 Series 90B ANNUNCIATOR INSTALLATION AND CONFIGURATION MANUAL
FIRST OUT, TRIPLE FLASH, FIRST OUT RESET, RESET
SEQUENCE CODE
ALARM
DEVICE
NORMAL
ALARM
SILENCE
ACKNOWLEDGE
(FLASH RESET)
FIRST OUT RESET
RETURN TO NORMAL
RESET
INITIAL
NEXT
INITIAL
NEXT
INITIAL
NEXT
INITIAL
NEXT
INITIAL
NEXT
RESET
TFSFR
M
VISUAL
INT. FAST
FAST
INT. FAST
FAST
SLOW
AUDIBLE
Note: The RESET and FIRST OUT RESET Pushbuttons are combined together at the same terminal.
FIRST OUT, TRIPLE FLASH, FIRST OUT RESET, RESET
SEQUENCE CODE
ALARM
DEVICE
NORMAL
ALARM
ACKNOWLEDGE
FIRST OUT RESET
RETURN TO NORMAL
RESET
INITIAL
NEXT
INITIAL
NEXT
INITIAL
NEXT
INITIAL
NEXT
RESET
TFSM
VISUAL
INT. FAST
FAST
SLOW
AUDIBLE
Note: The RESET and FIRST OUT RESET Pushbuttons are combined together at the same terminal.
RINGBACK, DUAL FLASH, LOCK IN UNTIL ACKNOWLEDGED
SEQUENCE
CODE
ALARM
DEVICE
NORMAL
ALARM
ACKNOWLEDGE
RETURN TO
NORMAL
RESET
ARR
ISA-R
VISUAL
FAST
SLOW
AUDIBLE
Ringback Audible
RINGBACK, DUAL FLASH, LOCK IN UNTIL ACKNOWLEDGED
SEQUENCE
CODE
ALARM
DEVICE
NORMAL
ALARM
SILENCE
ACKNOWLEDGE
(FLASH RESET)
RETURN TO
NORMAL
RESET
FRR
VISUAL
FAST
FAST
SLOW
AUDIBLE
Ringback Audible