• Disp: Select the type of data that must be
recorded for the device
Value - The current values of the device
FldAvg - The average value of the device
Test Val - The device test value
High - Highest value achieved by the device
Low - Lowest value achieved by the device
Contam - % Contamination of the device
CommQlt - % Communication quality of the device
*See Page 83, Device Statistics
-
The device value is the only parameter that is scanned by the panel at a fast rate.
All other statistics are updated once every 20 minutes. It is therefore pointless to
sample any statistic other than the device value at a rate faster than 1/20 min.
When 1/day is selected, then the time that the sample is taken is that set in the Test
Times of the Maintenance Menu (Page 157).