Day mode times
(SET TIMES MENU, 7, )
DAY MODE Thu 07/12/00 10:39:52
Monday :08:00 Friday :08:00
Tuesday :08:00 Saturday :08:00
Wednesday :08:00 Sunday :08:00
Thursday :08:00 Lnk :none
0. . 9, ^V, <>, E, X
Alarms: 0 Faults: 0 Cond.: 0 P: 1 SDZ
Return to Set Times Menu Page 68
Select item to be changed
or 0..9 change data in item (Unlock memory!)
Confirm change
*See also Night Mode Times, Page 76
Zones that are enabled for Day/Night operation (see Page 96 ) will be switched to DAY
Mode at the times indicated, provided Link is switched to None. A separate time for each
day of the week is allowed. A time setting of 00h00 causes no action.
Link:If Link is switched to Fire Brigade, the Day Mode times are set to 00h00 and the
times set in the Fire Brigade Off Times (Page 71) is used, if the Link is set to external
(EXT.), the Day Mode Times are controlled by the Day Mode Output. Link must be set to
None in order to use the Day Mode Times.
Day Mode uses the Day level alarm threshold set in the Device Setup Menus.

Table of Contents

Other manuals for Aritech FP2000 Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Aritech FP2000 Series and is the answer not in the manual?

Aritech FP2000 Series Specifications

General IconGeneral
BrandAritech
ModelFP2000 Series
CategoryFire Alarms
LanguageEnglish

Related product manuals