Area disable
(DISABLE MENU, 3, )
AREA DISABLE
Area :1 Adj 2 :0
Status :en Adj 3 :0
Coincidence :unlogged Adj 4 :0
Adj 1 :0 Adj 5 :0
0. . 9, ^V, <>, E, X
Alarms: 0 Faults: 1 Cond.: 0 P: 1 SDZ
Return to Disable Menu Page 193
Toggle between Area and Status
For Area field:
or 0..9 select area to be disabled/enabled
Confirm entry
For Status field:
select enable/disable
Confirm entry
The selected area is disabled/enabled from the system. A disabled area will still report
fires or faults occurring in the area. Only I/O operation to or from the area is disabled.
Existing fire or fault conditions will not be cancelled when the area is disabled. The fire or
fault will be cleared, and re-occur if they are still present, when the panel is reset.
Disable does not electrically disconnect the device from the loop. Disable should not
be used if maintenance is to be done on the loop or the devices. The loop must be
physically disconnected in this case.
The Coincidence and Adjacent Area settings are displayed on this screen for information
purposes only.
*See Area Menu (Page 99) for further information of the Area Menu.

Table of Contents

Other manuals for Aritech FP2000 Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Aritech FP2000 Series and is the answer not in the manual?

Aritech FP2000 Series Specifications

General IconGeneral
BrandAritech
ModelFP2000 Series
CategoryFire Alarms
LanguageEnglish

Related product manuals