Step-by-step LON device installation walkthru
Any LON device or -module can be connected to a FP2000 firepanel via a LON2000
module. Here is a step-by-step installation example for the FBP700:
1. Connect the FBP700 to the FP2000 (24V to supply, communication to LON2000)
2. Enable the LON port
EntryCode / 1-System / 1-Configuration / 4-Communication / 1-PortSetup
Toggle Port to LON
Toggle Allocation to LON
3. Install the FBP700
EntryCode / 1-System / 1-Configuration / 4-Communication / 5-LONDevices
Select Node = 1
4. Press service switch on FBP700
On the right half of the Screen (FP2000) you should see
Fldseq :1
FldType:FBP700
FldId: 001 Ver: 1.03 (Depending on which version of firmware is in the module)
FldNID:???????????? (12 characters Neuron id)
5. If the information appears as in (4) move the cursor to "Add"
(The "Add" field should now be highlighted.)
Press Enter.
The information in (4) moves to the left side of the screen
6. Reset the panel
7. The FBP700 is installed.

Table of Contents

Other manuals for Aritech FP2000 Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Aritech FP2000 Series and is the answer not in the manual?

Aritech FP2000 Series Specifications

General IconGeneral
BrandAritech
ModelFP2000 Series
CategoryFire Alarms
LanguageEnglish

Related product manuals