Fire brigade delay off times
(SET TIMES MENU, 3, )
FBRIG DELAY OFF Thu 07/12/00 10:39:52
Monday :18:00 Friday :18:00
Tuesday :18:00 Saturday :18:00
Wednesday :18:00 Sunday :18:00
Thursday :18:00
0. . 9, ^V, <>, E, X
Alarms: 0 Faults: 0 Cond.: 0 P: 1 SDZ
Return to Set Times Menu Page 68
Select item to be changed
or 0..9 change data in item (Unlock memory!)
Confirm change
The time each day that the Fire Brigade Delay is automatically switched from ON to OFF
is set in this menu. The time for each day of the week can be allocated. Note that the
switching of the delay from OFF to ON is a manual only operation using the Fire Brigade
Delay ON/OFF pushbutton with the keyswitch enabled.
If no automatic delay off operation is required, then the time 00h00 must be used, it is
ignored by the FP2000 fire panel. The Fire Brigade Delay can also be manually switched
off at any time using the front panel delay ON/OFF pushbutton.
*See Output Delays, Page 70

Table of Contents

Other manuals for Aritech FP2000 Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Aritech FP2000 Series and is the answer not in the manual?

Aritech FP2000 Series Specifications

General IconGeneral
BrandAritech
ModelFP2000 Series
CategoryFire Alarms
LanguageEnglish

Related product manuals