Local repeaters
(NETWORK, 2, )
LOCAL REPEATERS
L-Repeater No. :1
Status :dis
^V, <>, E, X
Alarms: 0 Faults: 1 Cond.: 0 P: 1 SDZ
Return to Network Menu Page 41
or 0..9 to select repeater number
Move to status field
Toggle dis/NET1 check/NET2 check/NET1 no check/NET2 no check (Unlock
memory!)
Confirm entry
The local repeater that will communicate with this FP2000 panel on the network, must be
assigned.
Local repeaters that are assigned to the network will be checked for communication on
the system. If a local repeater is assigned to "NET1/2 check", a fault warning will be
displayed in the event of a failure, but if assigned to "NET1/2 no check", the failure will
only be an action logged in the event buffer.