xx = term/assignment number
yy is used for timer assignment only
Expressions may contain any number of terms separated by operators, but only up to
nested expressions. Each term is separated by either an "(" or operator or operator ")".
Assignment can be Output, Marker or Timer.
The operators available are:
END
Delete*
Insert*
NULL
)=
) set-s
) reset-s
) set-e
) reset-e
AND
AND NOT
AND (
AND NOT (
OR
OR NOT
OR (
OR NOT (
(
NOT (
)
)
*INSERT and DELETE are editing functions and are used at the time of entering.
The Term/Assignments available are:
Input xx
Output xx
Marker xx
Timer xx
not Input xx
not Output xx
not Marker xx
not Timer xx
xx - parameter of term
Input xx = 1 to maximum Input Table
Output xx = 1 to maximum Output Table
Marker xx = 1 to 250
Timer xx = 1 to 250
yy time of timer = 1 to 240 seconds
-
When timer is used as an assignment, then the time yy is specified. When the timer is
used as a term in an expression, then the true/false state of the timer is used.

Table of Contents

Other manuals for Aritech FP2000 Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Aritech FP2000 Series and is the answer not in the manual?

Aritech FP2000 Series Specifications

General IconGeneral
BrandAritech
ModelFP2000 Series
CategoryFire Alarms
LanguageEnglish

Related product manuals