2 Zones
The total number of zones equipped on the FP2000 fire panel are proportioned amongst
the total number of devices that can be addressed by the fire panel.
E.g.: 16 zone 2 loop fire panel
maximum number of devices = 2 x 128 = 256
zone distribution = 256 / 16 = 16
Loop 1/1 to Loop 1/16 is assigned zone 1
Loop 1/17 to Loop 1/32 is assigned zone 2 etc.
Loop 2/1 to Loop 2/16 is assigned zone 9 etc.
Loop 2/113 to Loop 2/128 is assigned zone 16
64 zone 4 loops (devices = 512)
zone distribution = 8 devices/zone
3 Areas
The sixteen areas are equally distributed amongst the zones that are equipped on the
FP2000 fire panel.
e.g.: 16 zone fire panel
Zone 1 = Area 1
Zone 2 = Area 2, etc.
64 zone fire panel
Zone 1-4 = Area 1
Zone 5-8 = Area 2, etc.
4 System
Reserved
5 Loops
Enabled
6 Configuration
The memory is partitioned to the default configuration (see Memory Allocation, Page 33).
7 Logic
The logic table is set to a standard equation:
Input 1 = Output 1
Input 2 = Output 2, etc.
This equation is extended to the lower of:
- halve (see note) of the maximum number of logic lines allowed by the memory
allocation for logic
- the maximum number of inputs
- the maximum numbers of outputs
-
One equation comprises two logic lines. An allocation for logic of 300 would allow the
equation to be extended to: Input 150 = Output 150; provided that the number of inputs
and outputs are 150 or more.